Chiller lè-refwadi pou machin bòdi piki

Chiller lè-refwadi pou machin bòdi piki

Erè komen 1. Tanperati lwil oliv la twò wo: rezon ki fè: (1) Kapasite refwadisman lwil oliv la redwi. (2) Ekipman an nan febrifuj pou refwadi pi fre lwil oliv la ensifizan akòz bouche ekran filtre febrifuj la. (3) Portant mete. solisyon: (1) Ajiste tanperati lwil la...
Voye rechèch
Chat kounye a
Pwodwi Entwodiksyon

 

 

 

 

Karakteristik pwodwi

Otomatik, ekonomize enèji, personnalisable, gwo presizyon,Pwodiktivite segondè

Sèvis

Egzanp sipò tès,Sèvis konsiltasyon teknik gratis

Vann òf

Pri konpetitif

 

 

Erè komen

1. Tanperati lwil oliv la twò wo:

rezon:

(1) Kapasite refwadisman pi fre lwil oliv la redwi.

(2) Ekipman an nan febrifuj pou refwadi pi fre lwil oliv la ensifizan akòz bouche ekran filtre febrifuj la.

(3) Portant mete.

solisyon:

(1) Ajiste valv kontwòl tanperati lwil oliv la.

(2) Netwaye ekran filtè a nan filtè febrifuj la.

(3) Repare oswa ranplase kote yo pote apre demonte.


2.Main motè Surcharge:

rezon:

(1) vòltaj faz pouvwa a dezekilib.

(2) Gout vòltaj liy ekipman pou pouvwa a gwo.

(3) Kantite refrijeran refwadisman apwovizyone motè prensipal la pa ase.

solisyon:

(1) Pran mezi pou balanse vòltaj faz pouvwa a.

(2) Pran mezi pou redwi gout vòltaj liy ekipman pou pouvwa a.

(3) Tcheke ekran filtè filtè frijidè a epi netwaye ekran filtè a; louvri gwo valv inlet febrifuj la

 

Antretyen

Sekans nan ouvèti ak kanpe chiller la Pou asire ke lame lè-kondisyone a ka opere nòmalman apre yo fin kòmanse, li dwe asire ke:

① Kondansasyon an gen bon dissipation chalè, otreman li pral lakòz aparèy pwoteksyon wo-presyon chiller a aji ak sispann akòz tanperati a kondansasyon twòp ak presyon kondansasyon korespondan, oswa menm lakòz yon fonksyone byen.

②The cold water in the evaporator should circulate, otherwise the cold water temperature protection device will stop due to the low temperature of the cold water, or the low pressure protection device of the chiller will stop due to the low evaporation temperature and corresponding evaporation pressure, or even Cause the cold water in the evaporator to freeze and damage the equipment. Therefore, the sequence of starting the chiller is: (must be strictly followed) Cooling tower fan is on -> cooling water pump is on -> chilled water pump is on -> the chiller is on. The stopping sequence of the chiller is: (must be strictly followed) Stop——>Cooling tower fan stopped——>Cooling water pump stopped——>Ponp dlo frèt sispann

 

Prekosyon

① Lè fèmen, chiller la ta dwe fèmen yon demi èdtan anvan fen travay la, epi ponp chiller la ta dwe fèmen apre yo fin kite travay, ki se fezab pou ekonomize enèji, pandan y ap evite D 'ak pwoteje inite a.

② Anvan ou kouri sik refrijerasyon an, konfime ke tout tiyo nan tiyo sik chofaj la fèmen.

 